MEASUREMENT AND VERIFICATION OF ENERGY SAVINGS IN A TEN-STOREY HOSTEL BUILDING: COMPARATIVE ANALYSIS BETWEEN BASELINE AND REPORTING PERIODS
Keywords:
Measurement and Verification, energy-saving measures, LED lighting, institutional buildings, energy efficiencyAbstract
This study assesses the effectiveness of energy-saving measures (ESMs) in a ten-storey student hostel located in a Malaysia higher education institution through a comparative analysis of electricity consumption during a baseline period and a reporting period using the Measurement and Verification (M&V) protocol. The primary objective is to quantify the impact of ESMs, which involved replacing 536 units of 36W fluorescent lamps with 18W LED lamps and installing 74 timers for corridor lighting. Daily energy consumption data were collected over seven consecutive days in January 2020 (baseline) and March 2025 (reporting). The methodology followed the International Performance Measurement and Verification Protocol (IPMVP) to ensure reliable savings estimation. Findings indicate a 23.9% reduction in daily energy consumption, translating to RM4677 in monthly saving. This demonstrates the practical value of M&V in validating energy efficiency interventions. The study highlights the importance of systematic performance tracking in institutional energy management and recommends wider adoption of M&V practices for future energy efficiency projects in similar facilities.
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2025 Seminar Pembelajaran Sepanjang Hayat (SPSH) 2025